Posted by Jack Russell on September 23, 2005, 2:17 pm
I am in the design and planning stages of installing a tower for a 400w
Air-X wind generator. I need some input...How tall would you dare go using
1-1/2" sch 40 galv. pipe and if the run from the base of the tower to my
batteries is 150 feet, what conductor wire AGW would you recommend. Can I go
one size smaller with the ground? One more thing, minimum wire size for the
guys
I was thinking 33 feet tall, and 4 AGW for the conductor... and 8 lengths
(2 on each side) of 3/16" cable for the guys
Thanks, Paul...
Posted by Ecnerwal on September 23, 2005, 2:53 pm
> I was thinking 33 feet tall, and 4 AGW for the conductor... and 8 lengths
> (2 on each side) of 3/16" cable for the guys
If you are in the USA, the NEC will tell you what the minimum required
size of wire is. Depends on your amperage, which depends on your
voltage...
33 feet of 1-1/2" pipe sounds like an educational experience in how
expensive being cheap can be waiting to happen. Probably not waiting
long...
--
Cats, coffee, chocolate...vices to live by
Posted by Jack Russell on September 23, 2005, 4:32 pm
Thanks, You were a lot of help... -o
>> I was thinking 33 feet tall, and 4 AGW for the conductor... and 8
>> lengths
>> (2 on each side) of 3/16" cable for the guys
> If you are in the USA, the NEC will tell you what the minimum required
> size of wire is. Depends on your amperage, which depends on your
> voltage...
> 33 feet of 1-1/2" pipe sounds like an educational experience in how
> expensive being cheap can be waiting to happen. Probably not waiting
> long...
> --
> Cats, coffee, chocolate...vices to live by
Posted by Scott Willing on September 24, 2005, 9:58 am
On Fri, 23 Sep 2005 18:53:06 GMT, Ecnerwal
>> I was thinking 33 feet tall, and 4 AGW for the conductor... and 8 lengths
>> (2 on each side) of 3/16" cable for the guys
>If you are in the USA, the NEC will tell you what the minimum required
>size of wire is. Depends on your amperage, which depends on your
>voltage...
>33 feet of 1-1/2" pipe sounds like an educational experience in how
>expensive being cheap can be waiting to happen. Probably not waiting
>long...
1-1/2" sch 40 pipe is the design tower material according to the
manufacturer.
-=s
Posted by nicksanspam on September 25, 2005, 1:47 pm
>> I was thinking 33 feet tall, and 4 AGW for the conductor... and 8 lengths
>> (2 on each side) of 3/16" cable for the guys...
>33 feet of 1-1/2" pipe sounds like an educational experience...
Sounds like he needs spreaders as well as guy wires, like feed mill pipes..
Nick
> (2 on each side) of 3/16" cable for the guys