Posted by bealiba on September 13, 2007, 11:35 pm
System voltage 24 Volts
Battery Volts 2V
Daily load 3.5kWh
5 days autonomy
Battery bank capacity 1200Ah
Daily Depth of Discharge 13.5%
Array output required 180Ah/day
PV module output 5A
Garanteed current 4.5A
Number of modules in series 2
Number of parallel strings 9
Posted by philkryder on September 14, 2007, 12:58 am
On Sep 13, 8:35 pm, beal...@gmail.com wrote:
> System voltage 24 Volts
> Battery Volts 2V
> Daily load 3.5kWh
> 5 days autonomy
> Battery bank capacity 1200Ah
> Daily Depth of Discharge 13.5%
> Array output required 180Ah/day
> PV module output 5A
> Garanteed current 4.5A
> Number of modules in series 2
> Number of parallel strings 9
George -
Can one assume that if we needed 70kwh/day, that we simply multiply
your numbers by 20?
Posted by bealiba on September 14, 2007, 8:34 am
> On Sep 13, 8:35 pm, beal...@gmail.com wrote:
> > System voltage 24 Volts
> > Battery Volts 2V
> > Daily load 3.5kWh
> > 5 days autonomy
> > Battery bank capacity 1200Ah
> > Daily Depth of Discharge 13.5%
> > Array output required 180Ah/day
> > PV module output 5A
> > Garanteed current 4.5A
> > Number of modules in series 2
> > Number of parallel strings 9
> George -
> Can one assume that if we needed 70kwh/day, that we simply multiply
> your numbers by 20?
Well, no. I checked it and it seems to work. But you would be better
served by multiplying by ten and doubling the system voltage to 48
volts.
But you have asked this before. Nothing has changed in the technology
to reduce the cost.
Although, according to the world foremost expert on load reduction,
yes that would be wayne, all you need is to use an electric battery
charger to reduce your load.
Posted by Martin Riddle on September 14, 2007, 7:43 pm
> System voltage 24 Volts
> Battery Volts 2V
> Daily load 3.5kWh
> 5 days autonomy
> Battery bank capacity 1200Ah
> Daily Depth of Discharge 13.5%
> Array output required 180Ah/day
> PV module output 5A
> Garanteed current 4.5A
> Number of modules in series 2
> Number of parallel strings 9
Speaking of 24V modules, are any of those convertible to 12V?
Cheers
Posted by bealiba on September 14, 2007, 8:03 pm
> > System voltage 24 Volts
> > Battery Volts 2V
> > Daily load 3.5kWh
> > 5 days autonomy
> > Battery bank capacity 1200Ah
> > Daily Depth of Discharge 13.5%
> > Array output required 180Ah/day
> > PV module output 5A
> > Garanteed current 4.5A
> > Number of modules in series 2
> > Number of parallel strings 9
> Speaking of 24V modules, are any of those convertible to 12V?
> Cheers
This sizing was done using 75W 12V panels.
If you mean can your convert 24V panels to 12V some yes some no. It is
usually just a matter of where you connect to inside the Jbox on the
panel.
> Battery Volts 2V
> Daily load 3.5kWh
> 5 days autonomy
> Battery bank capacity 1200Ah
> Daily Depth of Discharge 13.5%
> Array output required 180Ah/day
> PV module output 5A
> Garanteed current 4.5A
> Number of modules in series 2
> Number of parallel strings 9