Posted by Alan C37 on August 30, 2006, 10:14 am
I am trying to design a ground loop water circulation system to warm (or
cool) air for an air source Heat Pump. Here I am concerned mainly with the
heating function. I am having problems with some theoretical details
concerning heat transfer rates and would appreciate any advice anyone cares
to offer.
The hypothetical situation is :-
A modern Air Source Heat Pump with the external unit located in a fairly
large (I have little idea of how large it must be yet!) insulated enclosure,
during the heating season. The manufacturer claims that the unit will give
a gain in heating with air temperatures as low as 10 deg F. I also
understand that putting the unit in an enclosure like this would invalidate
the maker's warranty but I might take the risk. The unit will be sized to
provide up to 12000 Btu/hr, or about 3.5 kW of heating
A long (perhaps 300 ft) loop of 4 inch diameter pipe buried about 4 ft in
sandy soil which may be somewhat damp during the heating season. Water (or
antifreeze) will be pumped around this loop, warmed by heat in the ground
and then passed through an array of finned pipes located on the air inlet
side of the blower in the heat pump outside unit.
The idea, of course, is to raise the air temperature enough to extend the
range of outside temperatures at which I can get useful heating performance
for the system and reduce my use of back-up baseboard heaters (reverse in
summer but that's another, easier, problem). The water in the pipe will be
warmed by the heat in the ground (at steady state) to perhaps 55 deg F, in
the area in which I live, even in the coldest month. I want the heat pump
input air to be at a minimum temperature of 30 deg F (preferably higher if
possible) since the heating performance will fall off quite rapidly at lower
temperatures. The output air might be significantly lower than this but
will have to be warmed up again by heat from the ground loop to 50 deg F or
so quickly enough to be capable of being recalculated at the higher
temperature. Given an input water temperature of 50 deg F I would expect an
outlet water temperature of about 35 deg F and the water to be circulating
at about 1 gallon (Imperial) per minute. This suggests that water would be
underground and moving along the pipe for about 2.5 hrs. There are other
problems but the bits of theory I am stuck on at present are:-
What volume of air do I need in the enclosure?
What rate must I pump the water at (the 1 gall per minute given above is
merely a guess at present)?
What is the minimum length of ground loop I could get away with?
Will the soil around the pipe have sufficient time to recover from the
cooling effect of the water in the pipe before the water returns to the heat
exchanger in the enclosure? This is my main problem and having no idea of
how heat would flow in the ground to the water in the pipe I find it
impossible to proceed with the design. I am seriously considering building
a test installation and actually pumping water around it over the coming
winter and acquiring adequate test data with various water flow rates. If
anyone can point me towards any existing valid theoretical or test data I
would be most grateful as it seems to be a bit more than my ageing brain can
deal with.
I should probably say that I am aware of the existence of actual ground
source heat pumps and have seen claims about their performance which look
quite good. I have had no useful responses from people who make these units
(maybe I haven't yet found the right manufacturer yet). I am convinced that
modern air source heat pumps are readily available and have very good
performance figures, reasonably low prices and are not expensive to install.
Even if I do not go ahead with the enclosed unit idea it will still be
economically well worthwhile to install an air source heat pump and accept
that my existing baseboard heaters will be used more often than I would
like. Other people's experience with these thing indicate that I should be
able to reduce my annual electrical costs from about $4000 to $3000 or less.
Adding the ground loop shows reasonable promise of significantly more
savings.
Thanks.
Alan C
--
acombellack@nspmsympatico.ca
--
Posted via a free Usenet account from http://www.teranews.com
Posted by Alan C37 on September 3, 2006, 9:16 am
I thought I had sent this yesterday but I don't see it on the NG so I am
trying again. Alan C
I am somewhat surprised that there has been no response to my post. I am
well aware that this is complicated and have only rudimentary ideas about
how to answer my own questions so may I rephrase my main problem a little?
Consider a loop of 4 inch diameter plastic pipe buried 4 ft deep in sandy,
snow covered soil. The initial temperature of the soil is 55 deg F. The
pipe is full of water which is being pumped around the loop at 0.16 cubic
feet per minute. The temperature of the water when it enters the loop is 35
deg F. I assume it has been circulating for a full day or more and the
system has reached a steady state. The question I need an answer to is
What will be the temperature of the water at the output end of the loop? I
doubt that it will be as high 55 deg F but I hope it will be significantly
more than 35 deg F. Any ideas would be gratefully received as I am having
problems even imagining how heat will flow under these circumstances.
Thank you,
Alan C
> I am trying to design a ground loop water circulation system to warm (or
> cool) air for an air source Heat Pump. Here I am concerned mainly with
> the heating function. I am having problems with some theoretical details
> concerning heat transfer rates and would appreciate any advice anyone
> cares to offer.
> I am somewhat surprised that there has been no response to my post. I am
> well aware that this is complicated and have only rudimentary ideas about
> how to answer my own questions so may I rephrase my main problem a little?
> Consider a loop of 4 inch diameter plastic pipe buried 4 ft deep in
> sandy, snow covered soil. The initial temperature of the soil is 55 deg
> F. The pipe is full of water which is being pumped around the loop at
> 0.16 cubic feet per minute. The temperature of the water when it enters
> the loop is 35 deg F. I assume it has been circulating for a full day or
> more and the system has reached a steady state. The question I need an
> answer to is - What will be the temperature of the water at the output end
> of the loop? I doubt that it will be as high 55 deg F but I hope it will
> be significantly more than 35 deg F. Any ideas would be gratefully
> received as I am having problems even imagining how heat will flow under
> these circumstances.
> Thank you,
> Alan C
>> I am trying to design a ground loop water circulation system to warm (or
>> cool) air for an air source Heat Pump. Here I am concerned mainly with
>> the heating function. I am having problems with some theoretical details
>> concerning heat transfer rates and would appreciate any advice anyone
>> cares to offer.
>
--
Posted via a free Usenet account from http://www.teranews.com
Posted by daestrom on September 3, 2006, 11:58 am
> I am trying to design a ground loop water circulation system to warm (or
> cool) air for an air source Heat Pump. Here I am concerned mainly with
> the heating function. I am having problems with some theoretical details
> concerning heat transfer rates and would appreciate any advice anyone
> cares to offer.
> The hypothetical situation is :-
> A modern Air Source Heat Pump with the external unit located in a fairly
> large (I have little idea of how large it must be yet!) insulated
> enclosure, during the heating season. The manufacturer claims that the
> unit will give a gain in heating with air temperatures as low as 10 deg F.
> I also understand that putting the unit in an enclosure like this would
> invalidate the maker's warranty but I might take the risk. The unit will
> be sized to provide up to 12000 Btu/hr, or about 3.5 kW of heating
> A long (perhaps 300 ft) loop of 4 inch diameter pipe buried about 4 ft in
> sandy soil which may be somewhat damp during the heating season. Water
> (or antifreeze) will be pumped around this loop, warmed by heat in the
> ground and then passed through an array of finned pipes located on the air
> inlet side of the blower in the heat pump outside unit.
> The idea, of course, is to raise the air temperature enough to extend the
> range of outside temperatures at which I can get useful heating
> performance for the system and reduce my use of back-up baseboard heaters
> (reverse in summer but that's another, easier, problem). The water in the
> pipe will be warmed by the heat in the ground (at steady state) to perhaps
> 55 deg F, in the area in which I live, even in the coldest month. I want
> the heat pump input air to be at a minimum temperature of 30 deg F
> (preferably higher if possible) since the heating performance will fall
> off quite rapidly at lower temperatures. The output air might be
> significantly lower than this but will have to be warmed up again by heat
> from the ground loop to 50 deg F or so quickly enough to be capable of
> being recalculated at the higher temperature. Given an input water
> temperature of 50 deg F I would expect an outlet water temperature of
> about 35 deg F and the water to be circulating at about 1 gallon
> (Imperial) per minute. This suggests that water would be underground and
> moving along the pipe for about 2.5 hrs. There are other problems but the
> bits of theory I am stuck on at present are:-
> What volume of air do I need in the enclosure?
> What rate must I pump the water at (the 1 gall per minute given above is
> merely a guess at present)?
> What is the minimum length of ground loop I could get away with?
> Will the soil around the pipe have sufficient time to recover from the
> cooling effect of the water in the pipe before the water returns to the
> heat exchanger in the enclosure? This is my main problem and having no
> idea of how heat would flow in the ground to the water in the pipe I find
> it impossible to proceed with the design. I am seriously considering
> building a test installation and actually pumping water around it over the
> coming winter and acquiring adequate test data with various water flow
> rates. If anyone can point me towards any existing valid theoretical or
> test data I would be most grateful as it seems to be a bit more than my
> ageing brain can deal with.
> I should probably say that I am aware of the existence of actual ground
> source heat pumps and have seen claims about their performance which look
> quite good. I have had no useful responses from people who make these
> units (maybe I haven't yet found the right manufacturer yet). I am
> convinced that modern air source heat pumps are readily available and have
> very good performance figures, reasonably low prices and are not expensive
> to install. Even if I do not go ahead with the enclosed unit idea it will
> still be economically well worthwhile to install an air source heat pump
> and accept that my existing baseboard heaters will be used more often than
> I would like. Other people's experience with these thing indicate that I
> should be able to reduce my annual electrical costs from about $4000 to
> $3000 or less. Adding the ground loop shows reasonable promise of
> significantly more savings.
What you are describing is a ground-source system with an intermediate air
exchange. Quite frankly, because of the intermediate air-exchange, it is
bound to be less effective than a direct ground-source unit. Unless the
price difference between ground-source and air-source-with-ground-loop is
really large, I would go with the direct ground-source unit.
As far as how much water you would need to circulate, you can get an
estimate by this calculation...
Q = Mrate * Cp *(Tin-Tout)
Where
Q is BTU/hr
Tin & Tout are degrees F
Cp = 1 BTU/lbm-F for water, about 0.7 for 50/50 antifreeze
Mrate is in lbm/hour
For water....
12000 = Mrate * 1.0 *(50 -35)
Mrate = 800 lbm/hr
800 lbm/hr is about 1.6 gpm
For antifreeze/water
12000 = Mrate * 0.7*(50-35)
Mrate = 1142 lbm/hr
1142 lbm/hr is about 2.3 gpm
But 12000 BTU/hr seems like a very low number for climates that get below
freezing for much of the winter. Are you sure about that number? My
conventional furnace is 80,000 BTU/hr. To replace it with a heat-pump that
runs the same amount of time, I would need water flow of...
80000 = Mrate * 1.0*(50-35)
Mrate = 5333 lbm/hr
5333 lbm/hr is about 10.7 gpm
And because my ground temperature at *six* feet down is only about 40F....
80000 = Mrate * 1.0*(40-35)
Mrate = 16000 lbm/hr
16000 lbm/hr is about 32 gpm
The only difficulty with ground loops (whether direct-ground-source heat
pumps, or your design) is calculating the amount of heat that can be
extracted on a sustained basis. Yes, the average ground temperature might
be as high as 55F where you are (in winter here in NY it is decidedly colder
than that at 4 feet), but it won't *stay* at 55F for days on out with you
extracting a lot of heat from it. It will start to develop a sort of curved
profile with the temperature at 4 ft in your neighbors land still at 55.
But as you get closer and closer to your buried line it will start to drop
off and get colder as it approaches the line. How 'steep' this profile gets
is a function of the type of soil (how well it conducts heat from
surrounding soil, ground-water such as you mentioned can help a lot) and how
much heat is being extracted on average per day per linear foot. (spacing
between adjacent 'runs' of tubing is also important).
If there is 'moving' ground water, it can be really beneficial as the ground
water can carry a lot of energy passed your system. Water from much deeper
can be a lot warmer and is often used in this way (open-loop, deep-well heat
pumps).
I suspect that manufacturers of ground-source systems haven't been too
responsive because of this variation. The success or failure of such a
system is largely determined by the ground-loop field. Deep-well systems,
'slinky-loops', straight tubes, in wet soil, dry soil, wells drilled
through solid rock, there are just so many variations that the manufacturer
that just puts together the heat-pump and heat-exchanger has little control
over.
It would be best if one could somehow measure the performance to expect from
a given soil condition/installation without the expense of burying a long
length of tubing. Then one could get an accurate idea of how much heat can
be extracted from some ground-loop installation and how big of an
installation is needed.
One thought about your idea. If a conventional ground-source heat pump has
a ground loop that underperforms, the whole unit has to switch to resistive
heating or some other back up when the temperature of the ground loop falls
too low. This can *really* hurt overall performane costs. With your
system, if you leave some provision for opening the enclosure, then *if* the
ground loop performance is not up to the task, you can open the enclosure
and run the unit as an air-source. Admittedly this may still be a bit
costly (poor ground loop performance is most likely in cold weather), but
the whole system isn't completely out-of-commission. Then the next year,
funds permitting, the ground loop could be expanded/updated.
And since you're currently using resistance heating (electric baseboard),
*any* amount of heat-pump operation (spring/fall mild-winter weather) will
reduce energy costs.
daestrom
P.S. I'd seriously think about using an antifreeze mixture. Then you can
operate the loop at much colder temperatures and freezing the ground water
can provide substantial energy for a short term need (say, one particularly
cold day or two).
Posted by SJC on September 3, 2006, 12:22 pm
I like combining solar thermal a with fluid source heat pump.
With a large water store, you can run the solar thermal collectors
at a very efficient point even on a cold day. If the air is 30F and
the water gets to 90F, then there is plenty of heat in say 1000 gallons
of water to extract with a heat pump. Running solar thermal collectors
at only 90F on a 30F day is efficient. Storing water at only 90F reduces
the loses in the tank. You would just have to find what kind of COP a
fluid source heat pump gets when you input warm water like 80-90F
instead of 50F water from a ground source.
You can find the efficiency of a flat plate solar thermal collector in the PDF
here.
http://www.sunearthinc.com/empire_series_flat_plate.htm
A 36F delta between air and water gets you over 50% of the available solar heat.
Here is one of many ground (fluid) source heat pump manufacturers.
http://www.hydronmodule.com/singlespeed.html
I would think that they have performance data like COP based on source
temperature.
>> I am trying to design a ground loop water circulation system to warm (or
cool) air for an air source Heat Pump. Here I am
>> concerned mainly with the heating function. I am having problems with some
theoretical details concerning heat transfer rates
>> and would appreciate any advice anyone cares to offer.
>> The hypothetical situation is :-
>> A modern Air Source Heat Pump with the external unit located in a fairly
large (I have little idea of how large it must be yet!)
>> insulated enclosure, during the heating season. The manufacturer claims that
the unit will give a gain in heating with air
>> temperatures as low as 10 deg F. I also understand that putting the unit in
an enclosure like this would invalidate the maker's
>> warranty but I might take the risk. The unit will be sized to provide up to
12000 Btu/hr, or about 3.5 kW of heating
>> A long (perhaps 300 ft) loop of 4 inch diameter pipe buried about 4 ft in
sandy soil which may be somewhat damp during the
>> heating season. Water (or antifreeze) will be pumped around this loop,
warmed by heat in the ground and then passed through an
>> array of finned pipes located on the air inlet side of the blower in the heat
pump outside unit.
>> The idea, of course, is to raise the air temperature enough to extend the
range of outside temperatures at which I can get
>> useful heating performance for the system and reduce my use of back-up
baseboard heaters (reverse in summer but that's another,
>> easier, problem). The water in the pipe will be warmed by the heat in the
ground (at steady state) to perhaps 55 deg F, in the
>> area in which I live, even in the coldest month. I want the heat pump input
air to be at a minimum temperature of 30 deg F
>> (preferably higher if possible) since the heating performance will fall off
quite rapidly at lower temperatures. The output air
>> might be significantly lower than this but will have to be warmed up again by
heat from the ground loop to 50 deg F or so quickly
>> enough to be capable of being recalculated at the higher temperature. Given
an input water temperature of 50 deg F I would
>> expect an outlet water temperature of about 35 deg F and the water to be
circulating at about 1 gallon (Imperial) per minute.
>> This suggests that water would be underground and moving along the pipe for
about 2.5 hrs. There are other problems but the bits
>> of theory I am stuck on at present are:-
>> What volume of air do I need in the enclosure?
>> What rate must I pump the water at (the 1 gall per minute given above is
merely a guess at present)?
>> What is the minimum length of ground loop I could get away with?
>> Will the soil around the pipe have sufficient time to recover from the
cooling effect of the water in the pipe before the water
>> returns to the heat exchanger in the enclosure? This is my main problem and
having no idea of how heat would flow in the ground
>> to the water in the pipe I find it impossible to proceed with the design. I
am seriously considering building a test
>> installation and actually pumping water around it over the coming winter and
acquiring adequate test data with various water flow
>> rates. If anyone can point me towards any existing valid theoretical or test
data I would be most grateful as it seems to be a
>> bit more than my ageing brain can deal with.
>> I should probably say that I am aware of the existence of actual ground
source heat pumps and have seen claims about their
>> performance which look quite good. I have had no useful responses from
people who make these units (maybe I haven't yet found
>> the right manufacturer yet). I am convinced that modern air source heat
pumps are readily available and have very good
>> performance figures, reasonably low prices and are not expensive to install.
Even if I do not go ahead with the enclosed unit
>> idea it will still be economically well worthwhile to install an air source
heat pump and accept that my existing baseboard
>> heaters will be used more often than I would like. Other people's experience
with these thing indicate that I should be able to
>> reduce my annual electrical costs from about $4000 to $3000 or less. Adding
the ground loop shows reasonable promise of
>> significantly more savings.
> What you are describing is a ground-source system with an intermediate air
exchange. Quite frankly, because of the intermediate
> air-exchange, it is bound to be less effective than a direct ground-source
unit. Unless the price difference between
> ground-source and air-source-with-ground-loop is really large, I would go with
the direct ground-source unit.
> As far as how much water you would need to circulate, you can get an estimate
by this calculation...
> Q = Mrate * Cp *(Tin-Tout)
> Where
> Q is BTU/hr
> Tin & Tout are degrees F
> Cp = 1 BTU/lbm-F for water, about 0.7 for 50/50 antifreeze
> Mrate is in lbm/hour
> For water....
> 12000 = Mrate * 1.0 *(50 -35)
> Mrate = 800 lbm/hr
> 800 lbm/hr is about 1.6 gpm
> For antifreeze/water
> 12000 = Mrate * 0.7*(50-35)
> Mrate = 1142 lbm/hr
> 1142 lbm/hr is about 2.3 gpm
> But 12000 BTU/hr seems like a very low number for climates that get below
freezing for much of the winter. Are you sure about
> that number? My conventional furnace is 80,000 BTU/hr. To replace it with a
heat-pump that runs the same amount of time, I would
> need water flow of...
> 80000 = Mrate * 1.0*(50-35)
> Mrate = 5333 lbm/hr
> 5333 lbm/hr is about 10.7 gpm
> And because my ground temperature at *six* feet down is only about 40F....
> 80000 = Mrate * 1.0*(40-35)
> Mrate = 16000 lbm/hr
> 16000 lbm/hr is about 32 gpm
> The only difficulty with ground loops (whether direct-ground-source heat
pumps, or your design) is calculating the amount of heat
> that can be extracted on a sustained basis. Yes, the average ground
temperature might be as high as 55F where you are (in winter
> here in NY it is decidedly colder than that at 4 feet), but it won't *stay* at
55F for days on out with you extracting a lot of
> heat from it. It will start to develop a sort of curved profile with the
temperature at 4 ft in your neighbors land still at 55.
> But as you get closer and closer to your buried line it will start to drop off
and get colder as it approaches the line. How
> 'steep' this profile gets is a function of the type of soil (how well it
conducts heat from surrounding soil, ground-water such as
> you mentioned can help a lot) and how much heat is being extracted on average
per day per linear foot. (spacing between adjacent
> 'runs' of tubing is also important).
> If there is 'moving' ground water, it can be really beneficial as the ground
water can carry a lot of energy passed your system.
> Water from much deeper can be a lot warmer and is often used in this way
(open-loop, deep-well heat pumps).
> I suspect that manufacturers of ground-source systems haven't been too
responsive because of this variation. The success or
> failure of such a system is largely determined by the ground-loop field.
Deep-well systems, 'slinky-loops', straight tubes, in
> wet soil, dry soil, wells drilled through solid rock, there are just so many
variations that the manufacturer that just puts
> together the heat-pump and heat-exchanger has little control over.
> It would be best if one could somehow measure the performance to expect from a
given soil condition/installation without the
> expense of burying a long length of tubing. Then one could get an accurate
idea of how much heat can be extracted from some
> ground-loop installation and how big of an installation is needed.
> One thought about your idea. If a conventional ground-source heat pump has a
ground loop that underperforms, the whole unit has
> to switch to resistive heating or some other back up when the temperature of
the ground loop falls too low. This can *really*
> hurt overall performane costs. With your system, if you leave some provision
for opening the enclosure, then *if* the ground loop
> performance is not up to the task, you can open the enclosure and run the unit
as an air-source. Admittedly this may still be a
> bit costly (poor ground loop performance is most likely in cold weather), but
the whole system isn't completely out-of-commission.
> Then the next year, funds permitting, the ground loop could be
expanded/updated.
> And since you're currently using resistance heating (electric baseboard),
*any* amount of heat-pump operation (spring/fall
> mild-winter weather) will reduce energy costs.
> daestrom
> P.S. I'd seriously think about using an antifreeze mixture. Then you can
operate the loop at much colder temperatures and
> freezing the ground water can provide substantial energy for a short term need
(say, one particularly cold day or two).
>
Posted by Anthony Matonak on September 3, 2006, 1:35 pm
SJC wrote:
> I like combining solar thermal a with fluid source heat pump.
> With a large water store, you can run the solar thermal collectors
> at a very efficient point even on a cold day.
...
I wonder if one couldn't create a solar thermal collector for the
ground over the geothermal loops simply by suspending sheets of
greenhouse plastic film an inch or two off the dirt. They would be
like cold frames or really flat greenhouses and as long as they
are kept clear of snow, they should warm the ground somewhat.
Anthony
> cool) air for an air source Heat Pump. Here I am concerned mainly with
> the heating function. I am having problems with some theoretical details
> concerning heat transfer rates and would appreciate any advice anyone
> cares to offer.
> I am somewhat surprised that there has been no response to my post. I am
> well aware that this is complicated and have only rudimentary ideas about
> how to answer my own questions so may I rephrase my main problem a little?
> Consider a loop of 4 inch diameter plastic pipe buried 4 ft deep in
> sandy, snow covered soil. The initial temperature of the soil is 55 deg
> F. The pipe is full of water which is being pumped around the loop at
> 0.16 cubic feet per minute. The temperature of the water when it enters
> the loop is 35 deg F. I assume it has been circulating for a full day or
> more and the system has reached a steady state. The question I need an
> answer to is - What will be the temperature of the water at the output end
> of the loop? I doubt that it will be as high 55 deg F but I hope it will
> be significantly more than 35 deg F. Any ideas would be gratefully
> received as I am having problems even imagining how heat will flow under
> these circumstances.
> Thank you,
> Alan C
>> I am trying to design a ground loop water circulation system to warm (or
>> cool) air for an air source Heat Pump. Here I am concerned mainly with
>> the heating function. I am having problems with some theoretical details
>> concerning heat transfer rates and would appreciate any advice anyone
>> cares to offer.
>
--